sentronSeries 5SVActive

SENTRON 5SV residual current operated circuit breakers (RCCB)

SENTRON 5SV

Siemens residual current operated circuit breakers (RCCB) from 16 A to 80 A, 2-pole and 4-pole, with 10 to 500 mA rated residual current and types AC, A, F and B

Price and delivery time are given after a technical review.

Overview

Overview

SENTRON 5SV is Siemens' residual current operated circuit breaker (RCCB). A summation current transformer encloses all conductors of the circuit, neutral included: in a healthy circuit the currents add up to zero, and if current leaks to earth through faulty insulation the RCCB trips the circuit. An RCCB has no overload or short-circuit protection, so a suitable miniature circuit breaker or fuse must sit upstream of it.

Read more

Range

Rated current 16 A to 80 A in two configurations: 2-pole (1P+N, 36 mm wide) and 4-pole (3P+N, 72 mm wide). Rated residual current (IΔn) is 10, 30, 100, 300 or 500 mA, depending on type and configuration. Rated voltage is normally 230 V for the 2-pole and 400 V for the 4-pole; versions for 24 to 125 V and for 500 V also exist. The 2-pole type B takes four modules (72 mm).

Types

The type says which residual current waveform the RCCB detects, and the load behind it decides the suitable type. AC detects sinusoidal AC residual current only and is not permitted in every country, so check local installation rules. A also detects pulsating DC and is used for single-phase loads with an electronic power supply; smooth DC up to 6 mA does not impair its tripping. F covers every waveform type A does and also detects mixed-frequency residual currents up to 1 kHz, such as the output of a single-phase frequency converter in a washing machine or heat pump; it trips with a short delay and tolerates smooth DC up to 10 mA. B and B+ detect smooth DC residual current on top of the type F waveforms and are used in 50/60 Hz three-phase systems upstream of rectifier circuits; B detects up to 2 kHz and B+ up to 20 kHz. In the 5SV these two types are built with SIGRES technology in the SIQUENCE series.

Tripping versions

[K] (super resistant) has a 10 ms delay that makes it more immune to false tripping from transient disturbances and withstands surge currents above 3 kA. [S] (selective) is for an upstream group switch that must trip selectively against downstream RCCBs and withstands surge currents above 5 kA. SIGRES is a version for severe ambient conditions with active condensation protection.

Operation

Every device has a test button. Siemens specifies a half-yearly periodic test (annually for SIGRES versions), and under certain conditions this interval can be extended. Typical mechanical life in the data sheets is 10 000 operating cycles.

Mounting and accessories

Mounting is on a DIN rail and the terminals take up to 35 mm². The neutral connects on the left or right and the supply from top or bottom (SIGRES: top only). Auxiliary switches, fault signal contacts, shunt trips, undervoltage releases and remote control mechanisms come from the same accessory system as the miniature circuit breakers. According to the catalog, an undervoltage release combined with an RCCB is not suitable for EMERGENCY-OFF or EMERGENCY-STOP circuits.

Features

  • Rated current 16 A to 80 A
  • 2-pole (1P+N, 36 mm) and 4-pole (3P+N, 72 mm)
  • Rated residual current 10, 30, 100, 300 and 500 mA
  • Types AC, A, F and B/B+ (SIQUENCE series)
  • Super-resistant [K], selective [S] and SIGRES versions for severe conditions
  • Typical mechanical life of 10 000 operating cycles on 5SV3 and 5SV4
  • Neutral connection left or right, supply from top or bottom
  • Accessory system shared with the miniature circuit breakers: auxiliary and fault signal contacts, shunt and undervoltage releases, remote control

Advantages

  • Standard pin busbars and the 5ST3 accessories shared with SENTRON miniature circuit breakers
  • The right type for each load: F for circuits with a single-phase converter, B for three-phase systems upstream of a rectifier
  • [K] and [S] versions to reduce false tripping and to grade between RCCBs
  • SIGRES version with condensation protection for severe conditions

Models and codes

Models and codes
ModelOrder codeCode typeAttributesRequest
5SV3, 2-pole, type A, 25 A, 30 mAکلید محافظ جان دوپل، تیپ A، ۲۵ آمپر، ۳۰ میلی‌آمپر، ۲۳۰ ولت5SV3312-6Exact code
Poles:
2 (1P+N)
Type:
A
Rated current:
25 A
Rated residual current:
30 mA
Rated voltage:
230 V AC
Tripping:
Instantaneous
Width:
36 mm (2 MW)
Short-circuit rating:
10 kA
Max. series fuse:
63 A
Weight:
187 g
Request 5SV3, 2-pole, type A, 25 A, 30 mA
5SV3, 2-pole, type A, 63 A, 30 mAکلید محافظ جان دوپل، تیپ A، ۶۳ آمپر، ۳۰ میلی‌آمپر، ۲۳۰ ولت5SV3316-6Exact code
Poles:
2 (1P+N)
Type:
A
Rated current:
63 A
Rated residual current:
30 mA
Rated voltage:
230 V AC
Tripping:
Instantaneous
Width:
36 mm (2 MW)
Short-circuit rating:
10 kA
Max. series fuse:
80 A
Weight:
211 g
Request 5SV3, 2-pole, type A, 63 A, 30 mA
5SV3, 2-pole, type F, 25 A, 30 mAکلید محافظ جان دوپل، تیپ F، ۲۵ آمپر، ۳۰ میلی‌آمپر، ۲۳۰ ولت؛ برای مدارهای دارای اینورتر تک‌فاز5SV3312-3Exact code
Poles:
2 (1P+N)
Type:
F
Rated current:
25 A
Rated residual current:
30 mA
Rated voltage:
230 V AC
Version:
Super resistant [K]
Request 5SV3, 2-pole, type F, 25 A, 30 mA
5SV3, 4-pole, type A, 40 A, 30 mAکلید محافظ جان چهارپل، تیپ A، ۴۰ آمپر، ۳۰ میلی‌آمپر، ۴۰۰ ولت5SV3344-6Exact code
Poles:
4 (3P+N)
Type:
A
Rated current:
40 A
Rated residual current:
30 mA
Rated voltage:
400 V AC
Tripping:
Instantaneous
Width:
72 mm (4 MW)
Short-circuit rating:
10 kA
Max. series fuse:
80 A
Weight:
316 g
Request 5SV3, 4-pole, type A, 40 A, 30 mA
5SV3, 4-pole, type A, 63 A, 300 mAکلید محافظ جان چهارپل، تیپ A، ۶۳ آمپر، ۳۰۰ میلی‌آمپر؛ برای حفاظت در برابر آتش‌سوزی و حفاظت خطا5SV3646-6Exact code
Poles:
4 (3P+N)
Type:
A
Rated current:
63 A
Rated residual current:
300 mA
Rated voltage:
230/400 V AC
Tripping:
Instantaneous
Width:
72 mm (4 MW)
Short-circuit rating:
10 kA
Max. series fuse:
100 A
Weight:
336 g
Request 5SV3, 4-pole, type A, 63 A, 300 mA
5SV3, 4-pole, type F, 63 A, 30 mAکلید محافظ جان چهارپل، تیپ F با تأخیر کوتاه‌مدت، ۶۳ آمپر، ۳۰ میلی‌آمپر، ۴۰۰ ولت5SV3346-3Exact code
Poles:
4 (3P+N)
Type:
F
Rated current:
63 A
Rated residual current:
30 mA
Rated voltage:
400 V AC
Tripping:
Short-time delayed
Frequency:
50/60 Hz
Width:
72 mm (4 MW)
Short-circuit rating:
10 kA
Max. series fuse:
100 A
Weight:
373 g
Request 5SV3, 4-pole, type F, 63 A, 30 mA
5SV3 SIQUENCE, 4-pole, type B, 25 A, 30 mAکلید محافظ جان چهارپل، تیپ B با فناوری SIGRES و تأخیر کوتاه‌مدت، ۲۵ آمپر، ۳۰ میلی‌آمپر؛ تشخیص جریان نشتی مستقیم صاف5SV3342-4Exact code
Poles:
4 (3P+N)
Type:
B
Rated current:
25 A
Rated residual current:
30 mA
Rated voltage:
400 V AC
Supply voltage range:
70 … 440 V AC
Tripping:
Short-time delayed, SIGRES
Frequency:
50/60 Hz
Width:
72 mm (4 MW)
Short-circuit rating:
10 kA
Max. series fuse:
100 A
Weight:
445 g
Request 5SV3 SIQUENCE, 4-pole, type B, 25 A, 30 mA
5SV4, 4-pole, type AC, 40 A, 30 mAکلید محافظ جان چهارپل، تیپ AC، ۴۰ آمپر، ۳۰ میلی‌آمپر، ۴۰۰ ولت؛ استفاده از تیپ AC در همهٔ کشورها مجاز نیست5SV4344-0Exact code
Poles:
4 (3P+N)
Type:
AC
Rated current:
40 A
Rated residual current:
30 mA
Rated voltage:
400 V AC
Tripping:
Instantaneous
Width:
72 mm (4 MW)
Short-circuit rating:
10 kA
Max. series fuse:
80 A
Weight:
315 g
Request 5SV4, 4-pole, type AC, 40 A, 30 mA
5SV5, 4-pole, type A, 40 A, 30 mAکلید محافظ جان چهارپل از سری 5SV5، تیپ A، ۴۰ آمپر، ۳۰ میلی‌آمپر؛ مشخصات آن با 5SV3 یکی نیست: ۶ کیلوآمپر، حداقل دمای محیط ۵ درجه زیر صفر و بدون امکان نصب لوازم جانبی5SV5344-6Exact code
Poles:
4 (3P+N)
Type:
A
Rated current:
40 A
Rated residual current:
30 mA
Rated voltage:
230/400 V AC
Short-circuit rating:
6 kA
Max. series fuse:
80 A
Mechanical life:
4 000 operating cycles
Ambient temperature:
-5 … +45 °C
Supplementary devices:
Not installable
Weight:
305.8 g
Request 5SV5, 4-pole, type A, 40 A, 30 mA

Technical specifications

Check the specifications against the data sheet of the exact code before ordering.
مشخصات عمومی
Rated current rangeRated current range16 … 80 A
PolesPoles2-pole (1P+N), 4-pole (3P+N)
Rated residual current IΔnRated residual current IΔn10, 30, 100, 300, 500 mA
Type (residual current waveform)Type (residual current waveform)AC, A, F, B, B+
Rated voltage UnRated voltage Un230 (2-pole), 400 (4-pole); 24 … 125 and 500 on special versions V AC
Operating frequencyOperating frequency50; 50/60; 50 … 400 (version dependent) Hz
Tripping versionsTripping versionsInstantaneous; short-time delayed [G]/[K]; selective [S]; SIGRES
حساسیت به شکل‌موج جریان نشتی
Type ACType ACSinusoidal AC residual current
Type AType ASinusoidal AC and pulsating DC; smooth DC up to 6 mA tolerated
Type FType FAs type A, plus mixed-frequency residual current up to 1 kHz; smooth DC up to 10 mA tolerated; short-time delayed
Type B / B+Type B / B+As type F, plus smooth DC; B detects up to 2 kHz, B+ up to 20 kHz
اتصال کوتاه و تحمل ضربه
Short-circuit current rating with series fuse (5SV3, 5SV4)Short-circuit current rating with series fuse (5SV3, 5SV4)10 kA
Surge current withstand 8/20 µsSurge current withstand 8/20 µs> 1 (type A, instantaneous); > 3 (type F and super-resistant [K]); > 5 (selective [S]) kA
مشخصات مکانیکی و اتصال
WidthWidth2-pole: 36 mm (2 MW); 4-pole: 72 mm (4 MW); 2-pole type B: 72 mm (4 MW)
Height × depthHeight × depth90 × 70 mm
Connectable conductor cross-section (one wire)Connectable conductor cross-section (one wire)0.75 … 35 (solid/stranded); 0.75 … 25 (finely stranded with end sleeve) mm²
Terminal tightening torqueTerminal tightening torque2.5 … 3.5 N·m
Neutral connection and supplyNeutral connection and supplyN right or left; supply top or bottom (SIGRES: top only)
Degree of protectionDegree of protectionIP20, if the distribution board is installed, with connected conductors
بهره‌برداری
Mechanical service life, typical (5SV3, 5SV4)Mechanical service life, typical (5SV3, 5SV4)10 000 operating cycles
Test button intervalTest button intervalHalf-yearly (SIGRES versions: annually); extendable under certain conditions
شرایط محیطی
Ambient operating temperature (5SV3, 5SV4)Ambient operating temperature (5SV3, 5SV4)-25 … +45 °C
Storage temperatureStorage temperature-40 … +75 °C
Overvoltage category / degree of pollutionOvervoltage category / degree of pollutionIII / 2
استاندارد
StandardsStandardsIEC/EN 61008 (VDE 0664-10), IEC/EN 61008-2-1 (VDE 0664-11), IEC/EN 61543 (VDE 0664-30), IEC/EN 62423 (VDE 0664-40)

Modules and accessories

  • Auxiliary switch 5ST3010 (1 NO + 1 NC)

    Auxiliary switch for switch-position indication; from the same accessory system as the miniature circuit breakers

  • Fault signal contact 5ST3020 (1 NO + 1 NC)

    Fault signal contact that signals automatic tripping of the device

  • Auxiliary switch and fault signal contact 5ST3062 (1 CO + 1 CO)

    Auxiliary switch and fault signal contact in one housing

  • Shunt trip 5ST3030 (110 … 415 V AC, 110 … 220 V DC)

    Shunt trip for remote tripping of the mounted device

  • Undervoltage release 5ST3040 (230 V AC, with auxiliary switch)

    Undervoltage release with integrated auxiliary switch; according to the catalog, its combination with an RCCB is not suitable for EMERGENCY-OFF/EMERGENCY-STOP circuits

  • Remote control mechanism 5ST3055 (power, 12 … 30 V AC / 12 … 48 V DC)

    Remote control mechanism; with adapter 5ST3820-6 for 2-module devices

Documents

  • Catalog

    Catalog extract LV 10, chapter 4: Residual Current Protective Devices / Arc Fault Detection Devices (AFDDs)

    Catalog extract LV 10, chapter 4: Residual Current Protective Devices / Arc Fault Detection Devices (AFDDs)

    Language: English · Version 04/2023

    View on the manufacturer's site(opens in a new tab)
  • Manual

    SENTRON Technology primer: Residual Current Protective Devices

    SENTRON Technology primer: Residual Current Protective Devices

    Language: English · Version 2016

    View on the manufacturer's site(opens in a new tab)
  • Other

    Siemens EcoTech Profile SEP000051: SENTRON 5SV RCCB

    Siemens EcoTech Profile SEP000051: SENTRON 5SV RCCB

    Language: English · Version 02/2025

    View on the manufacturer's site(opens in a new tab)
  • Data sheet

    Data sheet 5SV3344-6: Residual current operated circuit breaker, 4-pole, type A, 40 A, 30 mA, 400 V

    Data sheet 5SV3344-6: Residual current operated circuit breaker, 4-pole, type A, 40 A, 30 mA, 400 V

    Language: English

    View on the manufacturer's site(opens in a new tab)
  • Data sheet

    Data sheet 5SV3346-3: Residual current operated circuit breaker, 4-pole, type F, short-time delayed, 63 A, 30 mA, 400 V

    Data sheet 5SV3346-3: Residual current operated circuit breaker, 4-pole, type F, short-time delayed, 63 A, 30 mA, 400 V

    Language: English

    View on the manufacturer's site(opens in a new tab)
  • Data sheet

    Data sheet 5SV3342-4: Residual current operated circuit breaker, 4-pole, type B, short-time delayed, 25 A, 30 mA, 400 V, SIGRES

    Data sheet 5SV3342-4: Residual current operated circuit breaker, 4-pole, type B, short-time delayed, 25 A, 30 mA, 400 V, SIGRES

    Language: English

    View on the manufacturer's site(opens in a new tab)
  • Data sheet

    Data sheet 5SV4344-0: Residual current operated circuit breaker, 4-pole, type AC, 40 A, 30 mA, 400 V

    Data sheet 5SV4344-0: Residual current operated circuit breaker, 4-pole, type AC, 40 A, 30 mA, 400 V

    Language: English

    View on the manufacturer's site(opens in a new tab)
  • Data sheet

    Data sheet 5SV5344-6: Residual current operated circuit breaker, 4-pole, type A, 40 A, 30 mA, 400 V

    Data sheet 5SV5344-6: Residual current operated circuit breaker, 4-pole, type A, 40 A, 30 mA, 400 V

    Language: English

    View on the manufacturer's site(opens in a new tab)

Applications

  • Additional protection against electric shock (30 mA) in socket and lighting circuits
  • Fire protection against leakage currents (up to 300 mA)
  • Circuits with washing machines, heat pumps and other loads with a single-phase converter (type F)
  • Three-phase systems upstream of rectifier circuits (type B)
  • Selective group switch upstream of downstream RCCBs (version S)

Frequently asked questions

What is the difference between types AC, A, F and B?

AC detects sinusoidal AC residual current only; A also detects pulsating DC; F adds mixed-frequency currents on top of A (for example the output of a single-phase converter in a washing machine or heat pump); and B/B+ add smooth DC on top of F. The load behind the RCCB decides the type: a single-phase load with an electronic supply usually needs A, a load with a single-phase converter needs F, and a three-phase system upstream of a rectifier needs B. Type AC is not permitted in every country, and the Siemens data sheet itself warns to observe national installation regulations.

Does an RCCB also trip on overload and short circuit?

No. An RCCB detects residual current only and has no overload or short-circuit protection. A suitable miniature circuit breaker (for example a 5SL) or fuse must sit upstream of it or in series, selected according to the manufacturer's information: the data sheet of each article states the maximum permissible series fuse (between 63 A and 100 A in the data sheets read). The short-circuit current rating with back-up fuse is 10 kA on 5SV3 and 5SV4.

Should I choose 30 mA or 300 mA rated residual current?

Siemens' technology primer assigns a rated residual current of up to 30 mA to additional protection against electric shock, values above 30 mA to fault protection (indirect contact), and up to 300 mA to fire protection. These ranges overlap: a device above 30 mA and up to 300 mA can serve both fault protection and fire protection. Where a resistive fault can start a fire, for example radiant ceiling heating, 30 mA must be used. The final choice follows the electrical installation rules of your country.

How often must the test button be pressed?

Siemens specifies a half-yearly periodic test, annually for SIGRES versions; under certain conditions the interval can be extended, and those conditions are in the catalog and the device instructions. The test is also required when the installation is commissioned.

What do the [K], [S] and SIGRES versions mean?

[K] (super resistant) has a 10 ms delay that makes it more immune to false tripping from transient disturbances and withstands surge currents above 3 kA. [S] (selective) is for an upstream group switch that trips selectively against downstream RCCBs and withstands surge currents above 5 kA. SIGRES is a version for severe ambient conditions with active condensation protection.

What is the difference between an RCCB and an RCBO?

An RCCB detects residual current only and, when it trips, disconnects every circuit downstream. An RCBO (such as Siemens' 5SV1 and 5SU1) combines residual current detection with overload and short-circuit protection in one device, and if each circuit has its own RCBO only the faulty circuit trips.