Skip to main content
Kara TejaratMehr Aein
کلید اتوماتیک کمپکت زیمنس SENTRON 3VA1، سه پل ۲۵۰ آمپر با رله حرارتی-مغناطیسی TM240، نمای روبه‌رو

© Siemens AG

sentronSeries 3VAActive

SENTRON 3VA molded case circuit breakers (MCCB)

SENTRON 3VA

Siemens molded case circuit breakers from 16 A to 1600 A, with thermal-magnetic (3VA1) or electronic (3VA2) trip units and breaking capacity up to 200 kA at 415 V

Price and delivery time are given after a technical review.

Overview

Overview

SENTRON 3VA is Siemens' family of molded case circuit breakers (MCCBs) for protecting cables and lines, generators, motors and starters in low-voltage switchboards. All frame sizes share one accessory platform, and the family comes in two main ranges: 3VA1 for standard applications with a thermal-magnetic trip unit, and 3VA2 for demanding applications with an electronic trip unit, better selectivity, metering and a connection to a communication system. 3VA27 is the 1600 A frame and shares its trip units and accessories with the 3WL10 air circuit breaker. This page covers the IEC versions only; the UL versions (3VA5 and 3VA6) are separate families.

Read more

Frame sizes and rated current

3VA1 has six frame sizes: 3VA10 (100 A), 3VA11 (160), 3VA12 (250), 3VA13 (400), 3VA14 (630) and 3VA15 (1000 A). 3VA2 has seven frame sizes from 3VA20 (100 A) to 3VA26 (1250 A), and 3VA27 is the 1600 A frame with a rated current of 800 A to 1600 A. In line protection the rated current In runs from 16 A (3VA1) to 1600 A (3VA27).

Breaking capacity

The ultimate breaking capacity Icu at 415 V is 16 to 110 kA for 3VA1 (classes B, N, S, M, H and C) and 55 to 200 kA for 3VA2 (classes M, H, C, L and E); class E exists only up to 630 A, and 3VA27 reaches 110 kA. The rated operational voltage goes up to 690 V AC, but the breaking capacity at 690 V is much lower than at 415 V (only 6 kA for a class M 3VA24), so on a 690 V network read the row for that voltage in the catalog table or in the data sheet of the exact article.

Trip units

3VA1 uses the thermal-magnetic trip units TM210, TM220 and TM240 for line protection and TM120M for starter protection; on the TM240 both the overload setting Ir and the short-circuit setting Ii are adjustable. 3VA20 to 3VA26 use electronic trip units in three series: the 3-series (ETU320, ETU330, ETU340, ETU350) with a rotary switch, the 5-series (ETU550, ETU560) with a display, and the 8-series (ETU850, ETU860) with a display and an integrated measurement function; the M versions are for motor and starter protection. The letters LSIG stand for the overload (L), short-time delayed short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) functions. 3VA27 has the ETU320, ETU350 and ETU360 (rotary switches) and the ETU650 and ETU660 (display, measurement and communication capability).

Communication and metering

On 3VA2 the 5- and 8-series trip units connect through the COM060 module to the COM800 or COM100 data concentrator, and from there to PROFIBUS, PROFINET, Modbus RTU or Ethernet (Modbus TCP); the DSP800 display for the cubicle door and a 24 V module for an independent trip unit supply are also available. On 3VA27 the COM040 to COM043 modules work with the 6-series trip unit.

3VA or 3WL?

Three criteria decide it. Current: 3VA reaches 1600 A; above that only 3WL (up to 6300 A) or its successor 3WA is suitable. Breaking capacity: at 630 A and below, 3VA2 offers up to 200 kA at 415 V against up to 66 kA for the 3WL10. Duty: the 3WL air circuit breaker is utilization category B, has a withdrawable version on a guide frame, and the 3WL10 has a mechanical life of 20,000 cycles (3VA27: 10,000 cycles). Between 800 A and 1600 A the 3VA27 and the 3WL10 share a platform and have the same fixed-mounted dimensions.

3VA2 plus

The LV 10 catalog add-on of 08/2026 introduces a new range, 3VA2 plus: the same 3VA2 platform with the same dimensions and accessories, up to 630 A (3VA20 to 3VA24), with 4-, 7- and 9-series trip units, Bluetooth, USB-C, an integrated radio interface, the DAS+ maintenance mode and the COM120 and COM121 modules for Ethernet.

Features

  • 3VA1: thermal-magnetic trip unit for standard applications, frame sizes 100 A to 1000 A
  • 3VA2: electronic trip unit for demanding applications, frame sizes 100 A to 1250 A; 3VA27 adds the 1600 A frame
  • Rated current In from 16 A to 1600 A in line protection
  • Ultimate breaking capacity Icu at 415 V: 16 to 110 kA (3VA1) and 55 to 200 kA (3VA2)
  • Rated operational voltage up to 690 V AC and rated insulation voltage 800 V
  • 3-pole and 4-pole versions in every frame; 1-pole and 2-pole versions in the 3VA11 frame
  • Electronic trip units of the 3-, 5- and 8-series with LI, LSI and LSIG functions; M versions for motor and starter protection
  • 8-series: display and integrated measurement function; connection to PROFIBUS, PROFINET, Modbus RTU and Modbus TCP with COM060 and COM800/COM100
  • No derating up to 50 °C ambient temperature
  • Fixed-mounted, with plug-in and withdrawable kits and over 500 accessories, many of them shared across frame sizes
  • 3VA2 plus (08/2026 catalog): up to 630 A with Bluetooth, USB-C and the DAS+ maintenance mode

Advantages

  • Many accessories (auxiliary switches, releases, motor operators, communication modules) are shared across frame sizes, which simplifies stock keeping
  • Protection, metering (current, voltage, power, energy) and communication in one device with the 8-series trip unit
  • Very good selectivity in the 3VA2; selectivity and back-up protection tables are available in the Siemens documentation
  • Compact 3VA1: 70 mm depth and a 45 mm cover size for distribution boards up to 250 A
  • Between 800 A and 1600 A the 3VA27 shares trip units and accessories with the 3WL10 air circuit breaker

Models and codes

Models and codes
ModelOrder codeCode typeAttributesRequest
3VA11, 160 A frame, TM240, class Sفریم 3VA11 (۱۶۰ آمپر) با تریپ یونیت حرارتی‌مغناطیسی TM240، جریان نامی ۶۳ آمپر، ردهٔ ظرفیت قطع S (۳۶ کیلوآمپر)، سه‌پل با ترمینال جعبه‌ای3VA1163-4EF36-0AA0Exact code
Frame:
160 A
Rated current In:
63 A
Overload setting Ir:
44 … 63 A
Short-circuit setting Ii:
5 … 10 × In
Breaking capacity class:
S
Icu at 415 V:
36 kA
Poles:
3
Dimensions W × H × D:
76.2 × 130 × 70 mm
Lifecycle (SiePortal, 2026-11-02):
Active Product
Request 3VA11, 160 A frame, TM240, class S
3VA13, 400 A frame, TM240, class Mفریم 3VA13 (۴۰۰ آمپر) با تریپ یونیت TM240، جریان نامی ۴۰۰ آمپر، ردهٔ M (۵۵ کیلوآمپر)، سه‌پل با کیت مهره‌نگهدار3VA1340-5EF32-0AA0Exact code
Frame:
400 A
Rated current In:
400 A
Overload setting Ir:
280 … 400 A
Short-circuit setting Ii:
5 … 10 × In
Breaking capacity class:
M
Icu at 415 V:
55 kA
Poles:
3
Dimensions W × H × D:
138 × 248 × 110 mm
Lifecycle (SiePortal, 2026-11-02):
Active Product
Request 3VA13, 400 A frame, TM240, class M
3VA15, 1000 A frame, TM240, class Mبزرگ‌ترین فریم 3VA1 (۱۰۰۰ آمپر) با تریپ یونیت TM240، جریان نامی ۱۰۰۰ آمپر، ردهٔ M (۵۵ کیلوآمپر)، سه‌پل3VA1510-5EF32-0AA0Exact code
Frame:
1000 A
Rated current In:
1000 A
Overload setting Ir:
700 … 1000 A
Short-circuit setting Ii:
5 … 10 × In
Breaking capacity class:
M
Icu at 415 V:
55 kA
Poles:
3
Dimensions W × H × D:
210 × 320 × 120 mm
Lifecycle (SiePortal, 2026-11-02):
Active Product
Request 3VA15, 1000 A frame, TM240, class M
3VA22, 250 A frame, ETU350 LSI, class Mفریم 3VA22 (۲۵۰ آمپر) با تریپ یونیت الکترونیکی ETU350 (LSI)، جریان نامی ۲۵۰ آمپر، ردهٔ M (۵۵ کیلوآمپر)، سه‌پل3VA2225-5HN32-0AA0Exact code
Frame:
250 A
Rated current In:
250 A
Overload setting Ir:
100 … 250 A
Short-time setting Isd:
1.5 … 10 × Ir
Instantaneous setting Ii:
10 × In
Breaking capacity class:
M
Icu at 415 V:
55 kA
Poles:
3
Dimensions W × H × D:
105 × 181 × 86 mm
Lifecycle (SiePortal, 2026-11-02):
Active Product
Request 3VA22, 250 A frame, ETU350 LSI, class M
3VA24, 630 A frame, ETU320 LI, class Eفریم 3VA24 (۶۳۰ آمپر) با تریپ یونیت ETU320 (LI) و ردهٔ E با ظرفیت قطع ۲۰۰ کیلوآمپر در ۴۱۵ ولت؛ بالاترین ظرفیت قطع خانواده3VA2463-0HL32-0AA0Exact code
Frame:
630 A
Rated current In:
630 A
Overload setting Ir:
250 … 630 A
Instantaneous setting Ii:
1.5 … 9 × In
Breaking capacity class:
E
Icu at 415 V:
200 kA
Poles:
3
Dimensions W × H × D:
138 × 248 × 110 mm
Lifecycle (SiePortal, 2026-11-02):
Active Product
Request 3VA24, 630 A frame, ETU320 LI, class E
3VA24, 630 A frame, ETU860 LSIG, class Mفریم 3VA24 (۶۳۰ آمپر) با تریپ یونیت ETU860 (LSIG) سری ۸ با نمایشگر و اندازه‌گیری، قابل اتصال به شبکهٔ ارتباطی، ردهٔ M (۵۵ کیلوآمپر)3VA2463-5KQ32-0AA0Exact code
Frame:
630 A
Rated current In:
630 A
Overload setting Ir:
250 … 630 A
Short-time setting Isd:
0.6 … 9 × In
Instantaneous setting Ii:
1.5 … 9 × In
Ground-fault setting Ig:
0.2 … 1 × In, can be switched off
Breaking capacity class:
M
Icu at 415 V:
55 kA
Communication function:
Yes
Dimensions W × H × D:
138 × 248 × 110 mm
Lifecycle (SiePortal, 2026-11-02):
Active Product
Request 3VA24, 630 A frame, ETU860 LSIG, class M
3VA27, 1600 A frame, ETU320 LI, class Mفریم 3VA27 (۱۶۰۰ آمپر) ثابت با دستهٔ دستی و تریپ یونیت ETU320 (LI)، ردهٔ M (۵۵ کیلوآمپر)؛ هم‌پلتفرم با کلید هوایی 3WL103VA2716-5AB03-0AA0Exact code
Frame:
1600 A
Rated current In:
1600 A
Overload setting Ir:
640 … 1600 A
Instantaneous setting Ii:
1.5 … 15 × In
Breaking capacity class:
M
Icu at 415 V:
55 kA
Poles:
3
Communication function:
No
Dimensions W × H × D:
210 × 296 × 183 mm
Lifecycle (SiePortal, 2026-11-02):
Active Product
Request 3VA27, 1600 A frame, ETU320 LI, class M
3VA2 plus (3VA20 … 3VA24)ردیف جدید 3VA2 plus تا ۶۳۰ آمپر با تریپ یونیت سری ۴، ۷ و ۹، بلوتوث و USB-C؛ کد دقیق به فریم، جریان، ظرفیت قطع و تریپ یونیت بستگی دارد و پیش از سفارش باید در SiePortal تأیید شود3VA2…Example code
Frames:
3VA20 … 3VA24
Rated current In:
25 … 630 A
Interfaces:
Bluetooth, USB-C
Catalog:
LV 10 add-on 08/2026
Request 3VA2 plus (3VA20 … 3VA24)

Technical specifications

Check the specifications against the data sheet of the exact code before ordering.
مشخصات عمومی
Frame sizes (3VA1)Frame sizes (3VA1)100, 160, 250, 400, 630, 1000 A
Frame sizes (3VA2)Frame sizes (3VA2)100, 160, 250, 400, 630, 1000, 1250 A
Frame size (3VA27)Frame size (3VA27)1600 A
Rated current In (line protection)Rated current In (line protection)16 … 1600 A
Rated operational voltage UeRated operational voltage Ue690 V AC
Rated operational voltage Ue, 3VA11 1-pole and 2-poleRated operational voltage Ue, 3VA11 1-pole and 2-pole415 V AC
Rated insulation voltage UiRated insulation voltage Ui800 V
Rated insulation voltage Ui, 3VA27Rated insulation voltage Ui, 3VA271000 V
Rated impulse withstand voltage UimpRated impulse withstand voltage Uimp8 kV
Number of poles (1 and 2 only in 3VA11)Number of poles (1 and 2 only in 3VA11)1, 2, 3, 4
Reference ambient temperature for InReference ambient temperature for In50 °C
Standards (IEC 60947-3 for switch disconnectors)Standards (IEC 60947-3 for switch disconnectors)IEC 60947-2, IEC 60947-3
ظرفیت قطع
Icu at 380 … 415 V, 3VA1Icu at 380 … 415 V, 3VA116 … 110 kA
Icu at 380 … 415 V, 3VA2Icu at 380 … 415 V, 3VA255 … 200 kA
Icu at 380 … 415 V, 3VA27Icu at 380 … 415 V, 3VA2755 … 110 kA
Breaking capacity classes and Icu at 415 VBreaking capacity classes and Icu at 415 V3VA1: B 16, N 25, S 36, M 55, H 70, C 110; 3VA2: M 55, H 85, C 110, L 150, E 200; 3VA27: M 55, H 85, C 110 kA
Icu at 690 V, 3VA20 … 3VA24Icu at 690 V, 3VA20 … 3VA24M, H, C: 2 … 6; L: 25; E: 85 kA
تریپ یونیت
Thermal-magnetic trip units for line protection (3VA1)Thermal-magnetic trip units for line protection (3VA1)TM210, TM220, TM240
Thermal-magnetic trip unit for starter protection (3VA1)Thermal-magnetic trip unit for starter protection (3VA1)TM120M
Electronic trip units, 3-series, rotary switch (3VA2)Electronic trip units, 3-series, rotary switch (3VA2)ETU320 (LI), ETU330 (LIG), ETU340 (ELISA LI), ETU350 (LSI)
Electronic trip units, 5-series, display (3VA2)Electronic trip units, 5-series, display (3VA2)ETU550 (LSI), ETU560 (LSIG)
Electronic trip units, 8-series, display and measurement (3VA2)Electronic trip units, 8-series, display and measurement (3VA2)ETU850 (LSI), ETU860 (LSIG)
M versions for motor and starter protection (3VA2)M versions for motor and starter protection (3VA2)ETU310M, ETU350M, ETU550M, ETU860M
Trip units of 3VA27 with rotary switchTrip units of 3VA27 with rotary switchETU320 (LIN), ETU350 (LSIN), ETU360 (LSING)
Trip units of 3VA27 with display, measurement and communicationTrip units of 3VA27 with display, measurement and communicationETU650 (LSIN), ETU660 (LSING)
ارتباط و اندازه‌گیری
Communication path of the 5- and 8-series trip units (3VA2)Communication path of the 5- and 8-series trip units (3VA2)COM060 → COM800 / COM100 → PROFIBUS, PROFINET, Modbus RTU, Modbus TCP
External cubicle-door display (up to eight devices)External cubicle-door display (up to eight devices)DSP800
Auxiliary supply module of the trip unit (optional)Auxiliary supply module of the trip unit (optional)24 V DC
Communication modules of 3VA27 with the 6-series trip unitCommunication modules of 3VA27 with the 6-series trip unitCOM040 PROFIBUS, COM041 PROFINET, COM042 Modbus RTU, COM043 Modbus TCP
نصب و عمر کارکرد
Mounting versionsMounting versionsFixed, Plug-in, Withdrawable
Mechanical / electrical endurance of 3VA24, 630 A (cycles, AC-1, 380/415 V)Mechanical / electrical endurance of 3VA24, 630 A (cycles, AC-1, 380/415 V)20 000 / 5 000
Mechanical / electrical endurance of 3VA27, 1600 A (cycles, AC-1, 380/415 V)Mechanical / electrical endurance of 3VA27, 1600 A (cycles, AC-1, 380/415 V)10 000 / 2 000
Dimensions of 3VA27, 3-pole (W × H × D)Dimensions of 3VA27, 3-pole (W × H × D)210 × 296 × 183 mm
3VA2 plus (جدید)
Rated current of 3VA2 plus (frames 3VA20 … 3VA24)Rated current of 3VA2 plus (frames 3VA20 … 3VA24)25 … 630 A
3VA2 plus trip units3VA2 plus trip unitsETU420, ETU430, ETU450, ETU460, ETU750, ETU760, ETU950, ETU960, ETU410M, ETU450M, ETU960M
Wireless and communication interfacesWireless and communication interfacesBluetooth, USB-C, COM120 / COM121 (Ethernet)
Lowest Ir settingLowest Ir setting20 % In

Modules and accessories

  • COM060 communications module

    Communications module for the right-hand accessories compartment of the 3VA2 (including the trip unit supply); connects to the COM800/COM100 through the 3VA line

  • COM800 / COM100 data concentrators

    Data concentrators: the COM800 connects up to eight and the COM100 one 3VA2 breaker to Ethernet, and through optional modules to PROFIBUS DP, PROFINET and Modbus RTU

  • DSP800 external display

    Cubicle-door display for the status and measured values of up to eight devices

  • 24 V module

    Optional 24 V DC supply for the trip unit, including continuous operation of the display and of the 8-series measurement function

  • EFB300 external function box

    External function box for connection to the trip unit, for functions such as ZSI

  • TD300 / TD400 / TD500 test devices

    Test devices for testing and commissioning the electronic trip unit through its test interface

  • MO310 / MO320 motor operators and SEO520 stored energy operator

    Motor operators for remote switching; the MO310 mounts on the side and the MO320 on the front, and the SEO520 adds a stored energy mechanism

  • Plug-in and withdrawable kits

    Conversion kits that turn a fixed-mounted breaker into a plug-in or withdrawable version for 3VA1 and 3VA2 frames

Documents

Applications

  • Incomer and feeder breakers in industrial, infrastructure and building distribution boards
  • Cable and line protection against overload and short circuit
  • Generator protection
  • Motor and starter protection (TM120M, ETU310M, ETU350M, ETU550M, ETU860M)
  • Switch disconnectors to IEC 60947-3
  • DC circuits with the 3VA1, according to the DC breaking capacity table

Frequently asked questions

Is a 3VA enough or do I need a 3WL?

Decide on three criteria.

  • Current: the 3VA reaches 1600 A (3VA27). Above that only the 3WL (up to 6300 A) or its successor 3WA is suitable.
  • Breaking capacity: at 630 A and below, the 3VA2 offers up to 200 kA at 415 V, while the 3WL10 offers up to 66 kA. For a high prospective short-circuit current on a small incomer, the 3VA2 is the stronger choice.
  • Duty: the 3WL is utilization category B, has a withdrawable version on a guide frame, and the 3WL10 has a mechanical life of 20,000 cycles; the 3VA27 has 10,000 mechanical cycles.

Between 800 A and 1600 A the 3VA27 and the 3WL10 share a platform and have the same fixed-mounted dimensions. In every case size the rated current from the load current and the short-circuit current at the installation point.

What is the difference between 3VA1 and 3VA2?

The 3VA1 has a thermal-magnetic trip unit (TM210, TM220, TM240) and is meant for standard applications up to 1000 A; its breaking capacity is 16 to 110 kA at 415 V and it is also used on DC circuits. The 3VA2 has an electronic trip unit, a breaking capacity of 55 to 200 kA, better selectivity, a measurement function and a connection to a communication system; it is for AC only and reaches 1600 A with the 3VA27.

Which trip unit should I choose?

If only overload and short-circuit protection with simple settings is needed, the TM240 in the 3VA1 is enough. If a short-time delayed short circuit (S) for selectivity or a ground fault (G) is needed, choose an electronic trip unit: the 3-series with a rotary switch (ETU350 for LSI), the 5-series with a display, and the 8-series when metering and communication are also wanted. For motors and starters use the M versions (ETU310M, ETU350M, ETU550M, ETU860M), and in the 3VA1 the TM120M trip unit.

How do I read the article number 3VA1163-4EF36-0AA0?

The 3VA1 structure in the Siemens catalog is: 3VA11 is the 160 A frame; 63 is the maximum rated current of 63 A; 4 is a breaking capacity of 36 kA at 415 V; E is without neutral protection; F is the TM240 trip unit; 3 is 3-pole; 6 is box terminals; 0AA0 is the fixed end of the code. For a full 3VA2 or 3VA27 code, use the Siemens configurator instead of guessing.

Can a 3VA breaker be connected to a communication network?

Yes, but only with suitable electronic trip units. On the 3VA2 the 5- and 8-series trip units connect through the COM060 module to the COM800 data concentrator (up to eight breakers) or the COM100 (one breaker), and from there to PROFIBUS, PROFINET, Modbus RTU or Modbus TCP. On the 3VA27 the 6-series trip unit works with the COM040 to COM043 modules. The 3-series and thermal-magnetic trip units have no communication capability.

What is the 3VA2 plus and does it replace the 3VA2?

The 3VA2 plus is a new range introduced in the LV 10 catalog add-on of 08/2026: the same 3VA2 platform with the same dimensions, selectivity and accessories, up to 630 A, with 4-, 7- and 9-series trip units, Bluetooth, USB-C, the DAS+ maintenance mode and an Ir setting down to 20% of In. Siemens does not say that it retires the 3VA2 up to 630 A; the classic 3VA2 articles are still shown as 'Active Product' on SiePortal.

Need SENTRON 3VA molded case circuit breakers (MCCB)?

Send your order code or requirement; after a technical review we give you the price and delivery time.