Skip to main content
Kara TejaratMehr Aein
کلید مینیاتوری زیمنس SENTRON 5SL3، سه پل C16 با قدرت قطع ۴٫۵ کیلوآمپر، نمای سه‌رخ

© Siemens AG

sentronSeries 5SLActive

SENTRON 5SL miniature circuit breakers

SENTRON 5SL

Siemens miniature circuit breakers (MCB) from 0.3 A to 63 A with 4.5, 6 and 10 kA breaking capacity, B and C characteristics (D on the 5SL4), from 1-pole to 4-pole, for final-circuit protection

Price and delivery time are given after a technical review.

Overview

Overview

SENTRON 5SL is Siemens' miniature circuit breaker (MCB) for final circuits in the distribution boards of residential, commercial and infrastructure buildings. It protects cable and wiring against overload and short circuit and can also serve as a main switch to disconnect and isolate equipment. Siemens positions 5SL for basic applications and has optimized the 5SY and 5SP families for industrial circuits.

Read more

Three series, three breaking capacities

The core of the family differs only in breaking capacity and the characteristics offered: 5SL3 at 4.5 kA, 5SL6 at 6 kA and 5SL4 at 10 kA (to EN 60898-1). 5SL3 and 5SL6 come with characteristics B and C; 5SL4 adds D. Rated current is 0.3 A to 63 A in all three series, and dimensions and terminals are the same.

Tripping characteristics

The characteristic (trip curve) sets the multiple of rated current (In) at which the magnetic release trips instantly: B at 3 to 5 × In, C at 5 to 10 × In and D at 10 to 20 × In. B suits socket and lighting circuits, C suits circuits with higher starting currents such as lamps and motors, and D suits pulse-generating equipment such as transformers and solenoid valves. The thermal release, per EN 60898-1, does not trip at 1.13 × In and trips within one hour at 1.45 × In.

Pole configurations

Each series comes in six configurations: 1-pole (1 module = 18 mm), 1-pole+N and 2-pole (2 modules), 3-pole (3 modules), and 3-pole+N and 4-pole (4 modules). The 1-pole is rated 230/400 V, the 1-pole+N 230 V and the others 400 V.

Operating conditions

Rated voltage 230/400 V AC at 50/60 Hz and degree of protection IP20 with connected conductors. Ambient temperature is -25 to +45 °C (5SL4 up to +55 °C). Each device is used either on AC or on DC (up to 62.5 V per pole), never mixed.

Accessories

Auxiliary switches and fault signal contacts fit all three series; the 5SL4 also takes shunt trips, undervoltage releases and arc fault detection units (AFDD). The device is removed from the rail without tools.

Special versions

The compact 1-pole+N version in one module (5SL30 and 5SL60, 2 A to 40 A, 3 to 6 kA depending on rated current) and the 5SL6 COM version with measuring and communication functions also exist. Their data differ from the tables above and must be read from the data sheet of the exact article.

Features

  • Rated current 0.3 A to 63 A in all three series
  • Three series by breaking capacity: 5SL3 at 4.5 kA, 5SL6 at 6 kA and 5SL4 at 10 kA
  • Characteristics B and C on 5SL3 and 5SL6; B, C and D on 5SL4
  • Six pole configurations: 1-pole, 1-pole+N, 2-pole, 3-pole, 3-pole+N and 4-pole
  • Rated voltage 230/400 V AC, 50/60 Hz, to IEC/EN 60898-1
  • Screw terminals up to 35 mm² with room for pin busbars
  • Finger-safe terminals to EN 50274 and a sealable handle
  • Auxiliary switches and fault signal contacts; on 5SL4 also shunt trips, undervoltage releases and AFDD

Advantages

  • One family for every final circuit from 0.3 A to 63 A
  • 4.5, 6 or 10 kA breaking capacity without changing size: 90 mm high and 18 mm wide per pole
  • Quick replacement: the device comes off the rail and the busbar without tools
  • A systematic article number: series, breaking capacity, poles, current and characteristic can be read from the code
  • The same accessories as the other SENTRON miniature circuit breakers

Models and codes

Models and codes
ModelOrder codeCode typeAttributesRequest
5SL3, 1P, C16, 4.5 kAکلید مینیاتوری ۴٫۵ کیلوآمپر، تک‌پل، مشخصهٔ C، ۱۶ آمپر5SL3116-7Exact code
Series:
5SL3
Poles:
1P
Characteristic:
C
Rated current:
16 A
Breaking capacity Icn:
4.5 kA
Rated voltage:
230/400 V AC
Width:
18 mm (1 MW)
Weight:
137 g
Request 5SL3, 1P, C16, 4.5 kA
5SL6, 1P, B6, 6 kAکلید مینیاتوری ۶ کیلوآمپر، تک‌پل، مشخصهٔ B، ۶ آمپر؛ نمونهٔ مشخصهٔ B در سری 5SL65SL6106-6Exact code
Series:
5SL6
Poles:
1P
Characteristic:
B
Rated current:
6 A
Breaking capacity Icn:
6 kA
Rated voltage:
230/400 V AC
Width:
18 mm (1 MW)
Weight:
130 g
Request 5SL6, 1P, B6, 6 kA
5SL6, 1P, C16, 6 kAکلید مینیاتوری ۶ کیلوآمپر، تک‌پل، مشخصهٔ C، ۱۶ آمپر؛ نمونهٔ مشخصهٔ C برای مدارهای عمومی5SL6116-7Exact code
Series:
5SL6
Poles:
1P
Characteristic:
C
Rated current:
16 A
Breaking capacity Icn:
6 kA
Rated voltage:
230/400 V AC
Width:
18 mm (1 MW)
Power loss per pole:
1.8 W
Weight:
127 g
Request 5SL6, 1P, C16, 6 kA
5SL6, 1P+N, C16, 6 kAکلید مینیاتوری ۶ کیلوآمپر، تک‌پل+نول ۲۳۰ ولت، مشخصهٔ C، ۱۶ آمپر؛ نول هم قطع می‌شود5SL6516-7Exact code
Series:
5SL6
Poles:
1P+N
Characteristic:
C
Rated current:
16 A
Breaking capacity Icn:
6 kA
Rated voltage:
230 V AC
Neutral switching:
Yes
Width:
36 mm (2 MW)
Weight:
238 g
Request 5SL6, 1P+N, C16, 6 kA
5SL6, 3P, C16, 6 kAکلید مینیاتوری ۶ کیلوآمپر، سه‌پل ۴۰۰ ولت، مشخصهٔ C، ۱۶ آمپر5SL6316-7Exact code
Series:
5SL6
Poles:
3P
Characteristic:
C
Rated current:
16 A
Breaking capacity Icn:
6 kA
Rated voltage:
400 V AC
Width:
54 mm (3 MW)
Weight:
382 g
Request 5SL6, 3P, C16, 6 kA
5SL6, 4P, C63, 6 kAکلید مینیاتوری ۶ کیلوآمپر، چهارپل ۴۰۰ ولت، مشخصهٔ C، ۶۳ آمپر؛ بالاترین جریان نامی خانواده5SL6463-7Exact code
Series:
5SL6
Poles:
4P
Characteristic:
C
Rated current:
63 A
Breaking capacity Icn:
6 kA
Rated voltage:
400 V AC
Width:
72 mm (4 MW)
Power loss per pole:
5.2 W
Weight:
643 g
Request 5SL6, 4P, C63, 6 kA
5SL4, 1P, C0.3, 10 kAکلید مینیاتوری ۱۰ کیلوآمپر، تک‌پل، مشخصهٔ C، ۰٫۳ آمپر؛ پایین‌ترین جریان نامی خانواده5SL4114-7Exact code
Series:
5SL4
Poles:
1P
Characteristic:
C
Rated current:
0.3 A
Breaking capacity Icn:
10 kA
Request 5SL4, 1P, C0.3, 10 kA
5SL4, 1P, D10, 10 kAکلید مینیاتوری ۱۰ کیلوآمپر، تک‌پل، مشخصهٔ D، ۱۰ آمپر؛ برای بارهای پالس‌زا مانند ترانسفورماتور و شیر برقی5SL4110-8Exact code
Series:
5SL4
Poles:
1P
Characteristic:
D
Rated current:
10 A
Breaking capacity Icn:
10 kA
Rated voltage:
230/400 V AC
Ambient temperature:
-25 … +55 °C
Width:
18 mm (1 MW)
Weight:
155 g
Request 5SL4, 1P, D10, 10 kA
5SL4, 3P, C16, 10 kAکلید مینیاتوری ۱۰ کیلوآمپر، سه‌پل ۴۰۰ ولت، مشخصهٔ C، ۱۶ آمپر5SL4316-7Exact code
Series:
5SL4
Poles:
3P
Characteristic:
C
Rated current:
16 A
Breaking capacity Icn:
10 kA
Rated voltage:
400 V AC
Ambient temperature:
-25 … +55 °C
Width:
54 mm (3 MW)
Power loss per pole:
1.5 W
Weight:
455 g
Request 5SL4, 3P, C16, 10 kA

Technical specifications

Check the specifications against the data sheet of the exact code before ordering.
مشخصات عمومی
Rated current rangeRated current range0.3 … 63 A
Poles and configurationsPoles and configurations1P, 1P+N, 2P, 3P, 3P+N, 4P
Tripping characteristicTripping characteristicB, C (5SL3, 5SL6); B, C, D (5SL4)
Rated voltage UnRated voltage Un230/400 V AC
Maximum operational voltageMaximum operational voltage250/440 V AC
Maximum DC operational voltage per poleMaximum DC operational voltage per pole62.5 V DC
Rated frequencyRated frequency50/60 Hz
Rated impulse withstand voltage UimpRated impulse withstand voltage Uimp4 kV
Energy limitation classEnergy limitation class3 (B and C characteristics)
مشخصهٔ قطع
Instantaneous trip range, characteristic BInstantaneous trip range, characteristic B3 … 5 × In
Instantaneous trip range, characteristic CInstantaneous trip range, characteristic C5 … 10 × In
Instantaneous trip range, characteristic D (5SL4)Instantaneous trip range, characteristic D (5SL4)10 … 20 × In
Thermal test currents (In up to 63 A)Thermal test currents (In up to 63 A)1.13 × In: no trip within 1 h; 1.45 × In: trips within 1 h
قدرت قطع
Rated breaking capacity Icn (EN 60898-1), 5SL3 / 5SL6 / 5SL4Rated breaking capacity Icn (EN 60898-1), 5SL3 / 5SL6 / 5SL44.5 / 6 / 10 kA
Rated ultimate breaking capacity Icu (IEC/EN 60947-2), 5SL6 / 5SL4Rated ultimate breaking capacity Icu (IEC/EN 60947-2), 5SL6 / 5SL46 / 10 kA
مشخصات مکانیکی و اتصال
WidthWidth1P: 18 mm (1 MW); 1P+N and 2P: 36 mm (2 MW); 3P: 54 mm (3 MW); 3P+N and 4P: 72 mm (4 MW)
Height × depthHeight × depth90 × 76 mm
Connectable conductor cross-section (one wire)Connectable conductor cross-section (one wire)0.75 … 35 (solid/stranded); 0.75 … 25 (finely stranded with end sleeve) mm²
Terminal tightening torqueTerminal tightening torque2.5 … 3 N·m
Degree of protectionDegree of protectionIP20 with connected conductors; IP40 at the handle with distribution cover
Touch protection (EN 50274)Touch protection (EN 50274)Yes
Mounting positionMounting positionAny
شرایط محیطی
Ambient operating temperatureAmbient operating temperature-25 … +45 (5SL3, 5SL6); -25 … +55 (5SL4) °C
Storage temperatureStorage temperature-40 … +75 °C
استاندارد
Product standardProduct standardIEC/EN 60898-1; Icu to IEC/EN 60947-2

Modules and accessories

  • Auxiliary switch 5ST3010 (1 NO + 1 NC)

    Auxiliary switch for switch-position indication, 0.5 module wide; fits 5SL3, 5SL6 and 5SL4

  • Fault signal contact 5ST3020 (1 NO + 1 NC)

    Fault signal contact that signals automatic tripping on overload or short circuit, 0.5 module wide

  • Auxiliary switch and fault signal contact 5ST3062 (1 CO + 1 CO)

    Auxiliary switch and fault signal contact in one housing

  • Shunt trip 5ST3030 (110 … 415 V AC, 110 … 220 V DC)

    Shunt trip for remote tripping, 1 module wide; of 5SL3, 5SL6 and 5SL4 only on 5SL4

  • Undervoltage release 5ST3040 (230 V AC, with auxiliary switch)

    Undervoltage release with integrated auxiliary switch; of 5SL3, 5SL6 and 5SL4 only on 5SL4

  • Remote control mechanism 5ST3053 (basic, 12 … 30 V AC / 12 … 48 V DC)

    Remote control mechanism, 1.5 modules wide; with adapter 5ST3820-6 for 1 to 2 module devices or 5ST3820-7 for 3 to 4 module devices

  • Arc fault detection unit 5SM6021-2 (up to 16 A)

    Arc fault detection unit (AFDD) for 5SL4 1-pole+N devices (2 modules)

Documents

Applications

  • Socket and lighting circuits in residential and commercial buildings
  • Cooker circuits and machines in buildings
  • Meter panels and small distribution boards
  • Main switch for disconnecting and isolating equipment
  • Circuits with high starting currents such as lamps and motors (characteristic C), and transformers and solenoid valves (characteristic D on 5SL4)

Frequently asked questions

What is the difference between characteristics B, C and D, and which should I choose?

The characteristic sets the multiple of rated current at which the magnetic release trips instantly: B at 3 to 5 times, C at 5 to 10 times and D at 10 to 20 times. Siemens recommends B for socket and lighting circuits, C for circuits with higher starting currents such as lamps and motors, and D for pulse-generating equipment such as transformers and solenoid valves. D exists only on 5SL4, and not every rated current is offered in all three characteristics.

What is the difference between 5SL3, 5SL6 and 5SL4?

Breaking capacity and the characteristics offered: 5SL3 at 4.5 kA and 5SL6 at 6 kA (both with B and C), and 5SL4 at 10 kA (with B, C and D). The 5SL4 accepts an ambient temperature up to +55 °C and, of the three, is the only series that takes shunt trips, undervoltage releases and AFDD. Rated current is 0.3 A to 63 A and the dimensions are the same in all three.

Does the 5SL miniature circuit breaker also protect against electric shock?

No. The 5SL trips on overload and short circuit only and gives no protection against leakage current to earth. For additional protection of people, combine it with a residual current operated circuit breaker (RCCB such as the 5SV) or use an RCBO.

How do I read a 5SL article number?

For the standard devices (not the compact 5SL30 and 5SL60), taking 5SL6116-7: the digit after 5SL gives the series and breaking capacity (3 = 4.5, 6 = 6 and 4 = 10 kA); the next digit is the pole count (1 = 1-pole, 2 = 2-pole, 3 = 3-pole, 4 = 4-pole, 5 = 1-pole+N, 6 = 3-pole+N); the next two digits are the rated current (16 = 16 A; 14 = 0.3, 05 = 0.5, 01 = 1 and 15 = 1.6 A); and the digit after the dash is the characteristic (6 = B, 7 = C, 8 = D on 5SL4 only). So 5SL6116-7 is 6 kA, 1-pole, 16 A, characteristic C.

Can the 5SL be used on DC circuits?

Only at low voltage: up to 62.5 V DC per pole, and each device is used either on AC only or on DC only; mixed use is not permitted. For higher DC voltages Siemens has the universal-current 5SY5 and 5SP5 families (EN 60898-2).

Is the 5SL also suitable for industrial applications?

The 5SL is presented for basic building and infrastructure applications. Siemens has optimized the 5SY and 5SP families for industrial use; for an industrial circuit, compare the choice against the data sheets of those families as well.

Need SENTRON 5SL miniature circuit breakers?

Send your order code or requirement; after a technical review we give you the price and delivery time.